Difference between revisions of "Controls Meeting 27-Apr-2017"

From GlueXWiki
Jump to: navigation, search
 
(5 intermediate revisions by 2 users not shown)
Line 1: Line 1:
 
* Announcements
 
* Announcements
 
* Solenoid status (Tim,Beni,Nick)
 
* Solenoid status (Tim,Beni,Nick)
 +
** flow controllers for cooled leads
 
** solenoid in the summer  
 
** solenoid in the summer  
 
** small UPS removal
 
** small UPS removal
 
* BCAL PLC firmware upgrade (Nick)
 
* BCAL PLC firmware upgrade (Nick)
 +
  Current Revision 20.13 has known error with minor faults we see consistently(Type 03, Code93)
 +
    Version 20.14 is supposed to fix this. Fault is related to task overlap, may have masked the
 +
    fault we saw while running which was Ethernet port quit communicating with EPICs
 +
    https://rockwellautomation.custhelp.com/app/answers/detail/a_id/493328
 
* PLC-s not tripping MPODs when down (Nick)
 
* PLC-s not tripping MPODs when down (Nick)
* Alarms from BCAL (Nick, Hovanes)
+
[[BCAL-Chiller.MPOD Interlock.jpg]]
 +
* EPICS alarms from BCAL (Nick, Hovanes)
 
* BCAL chiller naming and labeling (Hovanes,Nick)
 
* BCAL chiller naming and labeling (Hovanes,Nick)
 
* Newport XPS-Q8 repairs (Hovanes)  
 
* Newport XPS-Q8 repairs (Hovanes)  
* CompCal Y-state status (Tim)
+
* CompCal Y-stage status (Tim)
 
* Other topics
 
* Other topics
  

Latest revision as of 09:20, 27 April 2017

  • Announcements
  • Solenoid status (Tim,Beni,Nick)
    • flow controllers for cooled leads
    • solenoid in the summer
    • small UPS removal
  • BCAL PLC firmware upgrade (Nick)
  Current Revision 20.13 has known error with minor faults we see consistently(Type 03, Code93)
   Version 20.14 is supposed to fix this. Fault is related to task overlap, may have masked the 
   fault we saw while running which was Ethernet port quit communicating with EPICs
   https://rockwellautomation.custhelp.com/app/answers/detail/a_id/493328
  • PLC-s not tripping MPODs when down (Nick)

BCAL-Chiller.MPOD Interlock.jpg

  • EPICS alarms from BCAL (Nick, Hovanes)
  • BCAL chiller naming and labeling (Hovanes,Nick)
  • Newport XPS-Q8 repairs (Hovanes)
  • CompCal Y-stage status (Tim)
  • Other topics

Time/Location

10:00AM Thursday 27-Apr-2017 CC B101