For alarms a dedicated MBBI record is implemented with 2 states NO_ALARM and Alarmed.
+
[[File:Alarm_calculation_scheme.jpg]]
The state itself calculated using CalcOut record.
+
The alarm would be triggered if:
+
If the channel is in enabled state and
+
{
+
  If channel is in neither of the following states:
+
  1. The channel is ramping up and
+
      |v0set:fbk - v0set| < ε
+
  2. The channel is on and
+
      |v0set:fbk - vmon| < δ and
+
      |v0set:fbk - v0set| < ε
+
}
+
 
+
[[File:Alarm_calculation_scheme.bmp]]
+
  
 
The δ and ε are different parameters for CAEN HV, WIENER LV abd BIAS modules.
 
The δ and ε are different parameters for CAEN HV, WIENER LV abd BIAS modules.

Revision as of 22:07, 16 April 2014

Alarm calculation scheme.jpg

The δ and ε are different parameters for CAEN HV, WIENER LV abd BIAS modules.

CAEN HV WIENER LV WIENER BIAS
δ 2V 0.1V 0.5V
ε 0.01V 0.01V 0.01V

Calcout record is recalculated and alarm state changed subsequently if one of inputs are changed achieved using posted monitors on input channels.