Line 7: Line 7:
 
# High-current HTS (17KA) vapor cooled leads
 
# High-current HTS (17KA) vapor cooled leads
 
#* Ettore will provide this information based on Sultan design
 
#* Ettore will provide this information based on Sultan design
# Fast protection system (external), with response time of ~0.5 s.
+
# Fast protection system (external), with response time of ~0.5 s. Commercial 4 parallel breakers 5KA each (20KA total), 2KV max. Two independent systems for redundancy.
#* Commercial 4 parallel breakers 5KA each (20KA total), 2KV max. Two independent systems for redundancy
+
 
#* Ettore will obtain details of these existing systems.
 
#* Ettore will obtain details of these existing systems.
  

Revision as of 08:40, 11 February 2011

Items for followup from previous meeting

  1. Power supply. Current ~ 15KA, voltage 5-10 V. (Could existing power supply 3KA/10V be converted to 6KA/5V?)
    • Elton can obtain cost estimates for this power supply
  2. Cryogenic plant: Primary circuit: Forced flow He at 4.5K, < 10g/s, ~5-10 bar, pressure drop < 2 bar. Secondary circuit: Deliver intermediate temperature He gas at 20-70 K to HTS vapor cooled current leads
    • Jonathan will investigate feasibility/cost of modifying existing refrigerator or purchasing new to deliver these requirements. Provide details to Ettore
  3. High-current HTS (17KA) vapor cooled leads
    • Ettore will provide this information based on Sultan design
  4. Fast protection system (external), with response time of ~0.5 s. Commercial 4 parallel breakers 5KA each (20KA total), 2KV max. Two independent systems for redundancy.
    • Ettore will obtain details of these existing systems.

Tentative Agenda

  1. Background (Elton)
  2. Discussion of items Ettore sent via e-mail

Minutes

Attending: