TASK | Primary Contact | Secondary Contact | PERIOD (days) | NEXT MAINTENANCE | LAST MAINTENANCE |
Gas Shed ODH | bunton@jlab.org | dallen@jlab.org | 365 | 04/16/25 | 04/16/24 |
Verify ODH System is functional 1. Observe the oxygen reading on the head in the Gas Shed (building 202, room 410) reads above 20.9%. 2. Cover the head with a plastic bag and fill the bag with inert gas (blowing into it can work too). 3. The alarm and lights should come on when the oxygen content falls below 19.5%. 4. Remove the bag from the Head, the alarm and lights should turn off. 5. Test complete |