Hall D Maintenance Status Long Description

Click the Last Maintenance date to update when the last maintenance was performed

Click the Task to EDIT the long description of this task

Click here to add a new item to the Hall D maintenance maintainer

TASK Primary Contact Secondary Contact PERIOD (days) NEXT MAINTENANCE LAST MAINTENANCE
Gas Shed ODH bunton@jlab.org dallen@jlab.org 365 04/16/25 04/16/24

Verify ODH System is functional 1. Observe the oxygen reading on the head in the Gas Shed (building 202, room 410) reads above 20.9%. 2. Cover the head with a plastic bag and fill the bag with inert gas (blowing into it can work too). 3. The alarm and lights should come on when the oxygen content falls below 19.5%. 4. Remove the bag from the Head, the alarm and lights should turn off. 5. Test complete