Hall D Maintenance Status Long Description

Click the Last Maintenance date to update when the last maintenance was performed

Click the Task to EDIT the long description of this task

Click here to add a new item to the Hall D maintenance maintainer

TASK Primary Contact Secondary Contact PERIOD (days) NEXT MAINTENANCE LAST MAINTENANCE
FDC Chiller Filter dallen@jlab.org bunton@jlab.org 240 11/24/24 03/29/24

Verify with Hall Work Coordinator that the FDC Chiller can be off line while Filter change out is done. Stopping flow of Chilled Water will shut Chiller down. Contact Lubomir-Ext.-5470 1-Turn off FDC Chiller and unplug from outlet. 2-Isolate Supply/Return Ball Valves from Chiller Manifold. 3-Release pressure from Filter by depressing Red Button on top of Housing. 4-Remove Cushion Clamp from Filter Housing. 5-Carfully Unscrew Housing and lower away from Filter. 6-Hold Filter and twist as you lower to break seal. 7-Install new Filter and verify that it is fully seated onto housing. 8-Install Housing over New Filter and Tighten 1/2 to 3/4 turn after O-ring makes contact. 9-Open Supply Ball Valve to Chiller Manifold. 10-Depress Red Button till all air is "Burped off". 11-Open Return Ball Valve to Chiller Manifold. 12- Plug Chiller back in and Switch on. 13-Verify Chiller is cooling back to the 20C set point. 14-Clean exterior cabinet. 15-Replacement Filtrine Filter #46.0535